Page 23 - PHI - Cierrapuertas
P. 23
ELR Application Charts
Simultaneous Pair of Doors 115 / 230 VAC
Pressing the push button retracts the latches on each ELR152
exit device. When both exit devices have retracted Battery Power
Supply
Backup
latches, the control modules in the power supply signals (Note 4)
the door operators to open the doors. The doors will
remain open until released by the Time Delay feature on 115 / 230 VAC Door
the Control Module. Operators
(Note 2)
Exit Exit
Device Device
(Note 3) (Note 3)
Push Push
Button Button
(Note 1) (Note 1)
4 Conductor (28 Gage Min.) Power Transfer Required. Ept-5 Concealed Power Transfer (See Page 29), Door Cord Or Hinge (Furnished By
Others)
Two Independent Pairs of Doors 115 / 230 VAC
Each pair of doors are operated
by pressing a push button which
retracts latch(es) on each exit ELR154
device. When both exit devices Power
Supply
have retracted latches the control Door Door
modules in the power supply Operators Operators
(Note 2)
signal the door operators (such as (Note 2)
the Precision D-4990 Low Energy
Operator) to open the doors. The Push Exit Exit Exit Exit Push
Button
Button
doors will remain open until released (Note 1) Device Device Device Device (Note 1)
by the Time Delay feature on the (Note 3) (Note 3) Push (Note 3) (Note 3)
Control Module. Button
(Note 4)
Push Push
Button Button
(Note 1) (Note 1)
4 Conductor (28 Gage Min.) Power Transfer Required. Ept-5 Concealed Power Transfer (See Page 29), Door Cord Or Hinge (Furnished By
Others)
Notes:
1. Push Button may be replaced with Card Reader, keypad,etc.,
providing normally open contacts and/or voltage inputs. See Wire Gage Maximum Wire Run Maximum Wire Run
for 22 Gage Power
hookup instructions in the ELR150 Installation Instructions. Transfer for 28 Gage Power
Transfer
2. Activation for Door Operators are provided by dry contact
on the Control Module. (2) wires must be run from the Power 16 75’ – 0” 55’ – 0”
Supply to each operator requiring control. 14 125’ – 0” 75’ – 0”
3. Each exit device requires (4) wires to operate. See chart to the 12 200’ – 0” ---
right for proper gage and wire run.
4. When Battery Backup is used, (2) 12 gage wires, less than 3 feet
long, connect batteries to Backup. Batteries must be mounted
outside the power supply enclosure. Battery Backup has a
Power Tap feature that can provide power to a Card Reader,
keypad system, etc. See page 22 for details.
Apex 2000 Series Touchbar Exit Devices 23