Delayed Egress (continued)
Door Position Switch – used in conjunction with the Delayed The (DE) devices are furnished with a decal which states:
Egress Exit Device, the following security features are added:
The Exit Device Alarm will sound if the door is not closed Push until alarm sounds.
when the device is armed. The Alarm will sound if the door is Door can be opened in 15 seconds.
forced open when the device is armed. While the device is in Note: A “30 Second” decal is provided when the 30 Second Delay option is specified.
the arming stage you may exit the opening. When the door
closes the arm/rearm time is cut short and the device is armed DE Electrical Specifications
preventing unauthorized tailgating through the opening. Voltage – 24VDC
Current Disarmed –100 mAmps
Current Armed – 3.2 Amps for 200 ms, 200 mAmps steady state
Door Widths – Available for 3’-0” and 4’-0” openings. For openings 3’-1”
and greater, please specify door width requirements.
Note: Not available for openings less than 3’-0”
To Order: specify prefix “DE” (e.g. DEFL2108)
The PS161-6 Power Supply is designed as a power source for
a variety of applications including Electric Locking, Exit Alarm
and Delayed Egress Exit Devices.
The Power Supply is a 120V input with a 12 or 24V output
rated at 6A. It can control up to 4 delayed egress exit devices.
Note: Adding additional loads to the PS161-6 Power Supply
(i.e., Card readers, Horns, etc.) may reduce the quantity of
Delay Egress Exit Devices controlled by the power
supply.
SPECIFICATIONS
Input
• Voltage: 120V AC, 60HZ
• Current: 3.5A AC
• Input fuse ratings: 5A/250V
• AC input is protected via an automatic reset circuit breaker
• Battery fuse ratings: 7.5A/32V
PS161-6 Power Supply (Required for Delayed
Output Egress Devices)
• Voltage: 12 or 24V
PS161-6 Power Supply
• Total output: 6 amps
• AC fail supervision (form “C” contacts).
• Power limit/output: 2 amps/per channel
• Outputs: 8 (For Delayed Egress applications: use only 4) • Unit is complete with power supply, enclosure, battery leads,
and lock.
• Ripple voltage: 910mV (Filtered and regulated outputs)
• LED indicators for AC Input, DC output, and battery backup status.
• Protection: Thermal and short circuit protection with auto Enclosure Dimensions
reset overload protection. • 12.5” x 13” x 3.25” (318mm x 330.2mm x 82.55mm)
Battery Backup Charger To Order: specify PS161-6 power supply
• Built-in charger for sealed lead acid or gel type batteries
(batteries not included)
• Maximum charge current: 1.54A
Wire Chart And OHMS Law
• Automatic switch over to stand-by is instantaneous with no Minimum Wire Gauge for 24 volts AC or DC
interruption
Additional Features Distance In Feet From Power Source
• Short circuit and overload protection. To Farthest Locking Device
• Supervised Fire Alarm disconnect (latching or non-latching) AMPS 25 50 75 100 150
on a normally open (NO) or normally closed (NC) trigger. 6.00 18 16 16 14 12
Apex 2000 Series Touchbar Exit Devices 25