Technical Details
Switch Settings Setting On Off
Factory default settings for normal operation; 1. Electric strike logic fail secure fail safe
all switches on the DIP switch are set to OFF. 2. Electric strike enabled disabled
3. PUSH side/PULL side PULL side PUSH side
4. PUSH and GO enabled disabled
5. Power close enabled disabled
6. N/A
7. N/A
8. N/A
Controller
1 2 10 11 12 21 16 13 17 18 19 20
3 15 4 5 6 7 8 9 14
1. TB-1 7. Self test button 14. Pot #6 open sweep speed
2. TB-3 8. Pot #2 Full open position adjustment 15. Pot #5 open check speed
3. TB-2 9. Pot #4 Stall force 16. Encoder plug input
4. Pot #3 not used 10. DIP switches (See chart above) 17. AC power in
5. Pot #1 Hold open time 0-28 seconds. 11. Digital readout 18. Fuse
Must be a minimum of 5 seconds after 12. Pot #7 opening torque, only needs 19. N/A
door fully open changed for use on heavier doors 20. Motor socket
6. Pot #9 Vestibule time delay 13. Pot #8 not used 21. N/A
Low Energy Operator D-4990 9